A Surge Impedance Loading(SIL)–Based Frame work for Transmission Line Monitoring and Predictive Fault Detection
| dc.contributor.author | Mugabe,Robert | |
| dc.contributor.author | Atim,Michael Robson | |
| dc.contributor.author | Obungoloch,Johnes | |
| dc.contributor.author | Wanzala,Jimmy Nabende | |
| dc.date.accessioned | 2026-08-24T12:54:49Z | |
| dc.date.issued | 2026 | |
| dc.description.abstract | Reliable operation of modern transmission networks requires not only post fault detection but also predictive identification of in- stability before fault escalation. This paper presents a probabilistic SIL-based frame work for real-time transmission line monitoring and predictive fault detection using receiving-end phasor measurements. Unlike conventional transient-driven methods, the proposed Approach formulates an adaptive SIL stability boundary incorporating voltage deviation and reactive power imbalance and transforms SIL exceed ancient hazard-based probabilistic risk metric. Monte Carlo simulations (N = 200 per loading level) validated ex-potential instability growth beyond the adaptive threshold, yielding a calibrated risk constant, k = 0.1746, with strong regression agreement, R2 = 0.9793. Implementation on a 220kV,200km transmission corridor and dynamic validation on an IEEE9-bus multimachine system demonstrated non-linear escalation off aultprobabilitybeyond110%SIL.Theframeworkachieved94.7% detection accuracy across 570 test disturbance sandidenti 7edhigh-risk conditions up to 50m sear Lier Hanan adaptive wavelet transform benchmark, while maintaining ower computational complexity. A two-dimensional SIL–reactive compensation risk map further enables proactive operator actions such as dynamic VAR support and preventive load shedding. The results establish SIL deviation as a computationally eBcientearly-warning indicator for transmission-line instability, enabling predictive default risk assessment and scalable deployment in wide-are a monitoring, and modern grid protection systems. | |
| dc.identifier.citation | Mugabe, R., Atim, M. R., Obungoloch, J., & Wanzala, J. N. (2026). A Surge Impedance Loading (SIL)–Based Framework for Transmission Line Monitoring and Predictive Fault Detection. Journal of Electrical and Computer Engineering, 2026(1), 8676039. | |
| dc.identifier.uri | https://ir.must.ac.ug/handle/123456789/4453 | |
| dc.language.iso | en_US | |
| dc.publisher | Journal of Electrical and Computer Engineering | |
| dc.rights | Attribution-NonCommercial-NoDerivs 3.0 United States | en |
| dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/3.0/us/ | |
| dc.subject | Adaptive | |
| dc.subject | threshold | |
| dc.subject | load ability analysis | |
| dc.subject | Predictive fault detection | |
| dc.subject | surge impedance loading | |
| dc.subject | voltage stability | |
| dc.title | A Surge Impedance Loading(SIL)–Based Frame work for Transmission Line Monitoring and Predictive Fault Detection | |
| dc.type | Article |
Files
Original bundle
1 - 1 of 1
Loading...
- Name:
- A Surge Impedance Loading (SIL)–Based Framework for Transmission Line Monitoring and Predictive Fault Detection.pdf
- Size:
- 6.02 MB
- Format:
- Adobe Portable Document Format
License bundle
1 - 1 of 1
Loading...
- Name:
- license.txt
- Size:
- 1.71 KB
- Format:
- Item-specific license agreed upon to submission
- Description: